Leslie-controls AEROFLOW SUPPLEMENT Special Balanced Mini-P Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Leslie-controls AEROFLOW SUPPLEMENT Special Balanced Mini-P. Leslie Controls AEROFLOW SUPPLEMENT Special Balanced Mini-P User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
12501 Telecom Drive, Tampa Florida 33637
Installation, Operating and
Maintenance Instructions
Supplement
10/2.5.1.C
Rev. 1
AEROFLOW SUPPLEMENT
Special Balanced Mini-P
TABLE OF CONTENTS
TABLE OF CONTENTS ............................................................................................................................. 1
ILLUSTRATION INDEX............................................................................................................................ 1
INSTALLATION ......................................................................................................................................... 1
MAINTENANCE ......................................................................................................................................... 1
ILLUSTRATION INDEX
F
IGURE
1
-
B
ALANCED
M
INI
-P ........................................................................................................................ 2
INSTALLATION
NOTE: Refer to Fig. 1 for installation.
1. Install seat gasket (504) into valve body
(306).
2. Install cage liner (505), seat/liner gasket
(506), seat (503) and body gasket (305) into
valve body (306).
3. Install plug seal and backup ring (507) into
seat (503). The plug seal and backup ring
(507) consist of 3 pieces. The think metal
ring goes in the ID of the seal (to prevent
collapse of the seal spring.) Use an o-ring
lubricant to prevent damaging the seal
during installation.
4. Slide the valve plug (502) into the valve seat
(503) slowly to not damage the plug seal and
backup ring (507).
5. Install the seal load ring (508).
6. Complete the bonnet (302) installation as
stated in the valve IOM.
MAINTENANCE
1. During routine maintenance the plug seal
and backup ring (507) need to be inspected
for wear and replaced as needed.
2. The valve IOM should be followed for all
operating and maintenance procedures.
CAUTION!
All warnings from valve IOM must be followed.